BXadmin:Power

From CCGB
Revision as of 18:40, 9 June 2011 by Phalenor (talk | contribs) (Measurements)

Jump to: navigation, search

Panels

UPSes

PDUs

Measurements

Conversions used:

  • 1 watt = 3.41214 BTU/h
  • 1 ton = 12,000 BTU/h

Therefor, 1 ton = 3516.854 watts


OPP Panel measurements

Jun 02, 2010

Panel CRP

  • A = 0
  • B = 0
  • C = 0
  • VA_total = 0

Panel CRP2

  • A = 55A
  • B = 45A
  • C = 60A
  • VA_total = 19200VA

Panel P509

  • A = 1.7A
  • B = 11A
  • C = 12.6A
  • VA_total = 3036VA

Panel SB5

  • A = 10A
  • B = 42A
  • C = 37A
  • VA_total = 10680VA

VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.

Room 509 VA_total = 32916 VA

Assuming VA = W (PF should not affect heat dissipation)...

  • Room 509 BTU/h = 112309 BTU/h
  • Room 509 tons = 9.36 tons

June 09, 2011

  • RACK-1 =
    • PDU-18[8+5 @208] -> UPS-13 -> SB5/14-16 =
    • ((zeus + pc9) -> PDU-14) + mulligan + jayne) -> UPS-12 =
  • RACK-2 =
    • (ift-1 + comandra) -> PDU-19 -> UPS-15 -> P509/5-7 = 1000W
    • xraid -> UPS-9 =
    • (herbie[] + pc4[] + horvitz[] + tortuga[]) -> UPS-10 =
  • RACK-3 =
    • (galaxy nodes + pc8) -> PDU-20[11+6 @208] -> UPS-8 -> SB5/15-17 =
  • RACK-4 =
    • (PDU-21[8+11 @208] + thumper[5.8 @208])-> UPS-7 -> SB5/21-23 =
  • RACK-5 =
    • 12*dell_nodes[2 @120] -> PDU-17 =
    • (1/2md1k-big + s1-array + 1/2md1k-1 + 1/2md1k-4 + 1/2md1k-5 + 1/2c14) -> UPS-5
    • (c8 + foundry + pc7 + s1-array + 1/2md1k-4 + 1/2md1k-6 + 1/2c14) -> UPS-6 -> CRP2-16
  • RACK-6 =
    • (node007..node012) -> PDU-6 -> CRP2-11
    • (node001..node006) -> PDU-7
    • (node013 + node014 + node015..node018) -> PDU-8 -> CRP2-1
    • (node025..node032) -> PDU-9 -> CRP2-14
    • (node019..node024) -> PDU-10
    • (1/2lux + 1/2s2 + 1/2s3 + 1/2md1k-3 + 1/2linne + 1/2xraid) -> UPS-2
    • (1/2xraid + 1/2s2 + 1/2s3 + 1/2lux + 1/2md1k-3 + 1/2md1k-2) -> UPS-3
    • (1/2md1k-2 + 1/2md1k-1 + 1/2md1k-5 + 1/2md1k-6 + 1/2md1k-big) -> UPS-4
  • RACK-7 =
    • (okinawa + switch) -> PDU-4 -> UPS-1
    • (9 okinawa nodes) -> PDU-5 -> P509/6-8
    • (7 okinawa nodes) -> PDU-22 -> CRP2/15-17
    • (huck md1k and PE2850) -> CRP2/11
  • RACK-8 =
    • PDU-23[2+1 @208] -> UPS-14 -> P509/9-11

machine current reference

  • zeus = 1.7A x2 @120V
  • carbonite promise sata RAID = 0.75A x2 @120V
  • carbonite = 3.7A x2 @120V
  • v880 2/3 power supplies, 3 CPU boards = ~5A x2 @120V
(10) PE 1950 - 2x Quad Core 2.83GHz, 16GB RAM, 146GB 15K 3.5" SAS, 1 PS
        powered off - 0.26A @120V pk, 0.16A @120V avg
        OS running, no load - 1.85A @120V pk, 1.73A @120V avg
        OS running, make -j32 - 2.73A @120V pk, 2.25A @120V avg

(32) linne darwin compute node
        powered off - 0.20A @120V pk, 0.10A @120V avg
        OS running, no load - 1.40A @120V pk, 1.15A @120V avg
        OS running, forked du -hs /scratch - 1.83A @120V pk, 1.65A @120V avg

(2) Xserve RAID
        7.6A/3.6A

(4) MD1K - 12x 3.5" SATA
        2x C13
        2.00A @208V

Foundry EdgeIron
        48W (.4A@120, .2A@208)

(10) Okinawa and compute nodes, 8x Xeon
        4.0A@120, 2.0A@208

SunFire 480R - 2x 1.2GHz US3+, 8GB (pilica)
        3.2A@120

StorEdge 3300
        1.5A@120

OptiPlex GX240 (minidb)
        3/1.5 ?

(10) PowerEdge 2650 (galaxy cnode)
        2.5A@120, 1.25A@208

PE 2950 - 8x2.83GHz, 32gb, 6x 3.5" SATA (baker)
        4A/2A

PE 2950 - 8x2.83GHz, 32gb, 4x 2.5" SAS (badger)
        3.74A/1.87A

PE 2970 - 8xAMD 2356, 16gb, 6x 3.5" sata (apollo)
        3.3A/1.65A

IBM x3550 - 4x3.0GHz Xeon 5160, 32gb (atlas)
        ~3A/1.5A ?

(2) IBM x3550 - 8x3.16GHz Xeon 5460, 32gb (c10, c11)
        ~4A/2A ?

IBM x3550 - 4x2.66GHz Xeon 5150, 32gb (frisell)
        ~3A/1.5A ?

Relion 230 - 4x2.8GHz Xeon, 2gb, 6x 3.5" PATA (horvitz)
        ~3/1.5A ?

Relion 140 - 4x2.8GHz Xeon, 3gb, 1x 146GB U320 scsi (tortuga)
        ~2A/1A ?

Altus 3150 - 2xAMD 250, 4gb, bunch o' sata (herbie)
        ~3A/1.5A ?

Relion 2000 - 4x2.8GHz Xeon, 4gb, 3ware 9500s-8 (8 3.5" sata) (scofield)
        ~3/1.5 ?

Altus 1300 - 2xAMD 256, 8gb, 2x 3.5" sata (mulligan)
        ~3/1.5 ?

IBM x3455 - 4x AMD 2218, 4gb, ? (coltrane)
        ~3/1.5 ?

IBM DS4200 - 8x 3.5" SATA, 2x 4Gb FC RAID
        ~4/2 ?

Sun x4540 (thumper)
        10/5.8