BXadmin:Power

From CCGB
Revision as of 15:09, 2 June 2010 by Phalenor (talk | contribs) (OPP Panel measurements)

Jump to: navigation, search

Panels

UPSes

PDUs

Measurements

OPP Panel measurements

Jun 02, 2010

Panel CRP

  • A = 0
  • B = 0
  • C = 0

VA_total = 0

Panel CRP2

  • A = 55A
  • B = 45A
  • C = 60A

VA_total = 19200VA

Panel P509

  • A = 1.7A
  • B = 11A
  • C = 12.6A

VA_total = 3036VA

Panel SB5

  • A = 10A
  • B = 42A
  • C = 37A

VA_total = 10680VA

VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.

Room 509 VA_total = 32916 VA

Assuming VA = W (PF should not affect heat dissipation)... Room 509 BTU/h = 112309 BTU/h Room 509 tons = 9.36 tons