Difference between revisions of "BXadmin:Power"

From CCGB
Jump to: navigation, search
(Created page with '= Panels = = UPSes = = PDUs =')
 
Line 4: Line 4:
  
 
= PDUs =
 
= PDUs =
 +
 +
= Measurements =
 +
 +
== OPP Panel measurements ==
 +
=== Jun 02, 2010 ===
 +
CRP
 +
* A = 0
 +
* B = 0
 +
* C = 0
 +
VA_total = 0
 +
 +
CRP2
 +
* A = 55A
 +
* B = 45A
 +
* C = 60A
 +
VA_total = 19200VA
 +
 +
P509
 +
* A = 1.7A
 +
* B = 11A
 +
* C = 12.6A
 +
VA_total = 3036VA
 +
 +
SB5
 +
* A = 10A
 +
* B = 42A
 +
* C = 37A
 +
VA_total = 10680VA
 +
 +
Room 509 VA_total = 32916 VA
 +
 +
Assuming VA = W (PF should not affect heat dissipation)...
 +
Room 509 BTU/h = 112309 BTU/h
 +
Room 509 tons = 9.36 tons

Revision as of 14:07, 2 June 2010

Panels

UPSes

PDUs

Measurements

OPP Panel measurements

Jun 02, 2010

CRP

  • A = 0
  • B = 0
  • C = 0

VA_total = 0

CRP2

  • A = 55A
  • B = 45A
  • C = 60A

VA_total = 19200VA

P509

  • A = 1.7A
  • B = 11A
  • C = 12.6A

VA_total = 3036VA

SB5

  • A = 10A
  • B = 42A
  • C = 37A

VA_total = 10680VA

Room 509 VA_total = 32916 VA

Assuming VA = W (PF should not affect heat dissipation)... Room 509 BTU/h = 112309 BTU/h Room 509 tons = 9.36 tons