Difference between revisions of "BXadmin:Power"

From CCGB
Jump to: navigation, search
(OPP Panel measurements)
(Jun 02, 2010)
Line 13: Line 13:
 
* B = 0
 
* B = 0
 
* C = 0
 
* C = 0
VA_total = 0
+
* VA_total = 0
  
 
Panel CRP2
 
Panel CRP2
Line 19: Line 19:
 
* B = 45A
 
* B = 45A
 
* C = 60A
 
* C = 60A
VA_total = 19200VA
+
* VA_total = 19200VA
  
 
Panel P509
 
Panel P509
Line 25: Line 25:
 
* B = 11A
 
* B = 11A
 
* C = 12.6A
 
* C = 12.6A
VA_total = 3036VA
+
* VA_total = 3036VA
  
 
Panel SB5
 
Panel SB5
Line 31: Line 31:
 
* B = 42A
 
* B = 42A
 
* C = 37A
 
* C = 37A
VA_total = 10680VA
+
* VA_total = 10680VA
  
 
VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.
 
VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.
Line 38: Line 38:
  
 
Assuming VA = W (PF should not affect heat dissipation)...
 
Assuming VA = W (PF should not affect heat dissipation)...
Room 509 BTU/h = 112309 BTU/h
+
 
Room 509 tons = 9.36 tons
+
* Room 509 BTU/h = 112309 BTU/h
 +
* Room 509 tons = 9.36 tons

Revision as of 14:10, 2 June 2010

Panels

UPSes

PDUs

Measurements

OPP Panel measurements

Jun 02, 2010

Panel CRP

  • A = 0
  • B = 0
  • C = 0
  • VA_total = 0

Panel CRP2

  • A = 55A
  • B = 45A
  • C = 60A
  • VA_total = 19200VA

Panel P509

  • A = 1.7A
  • B = 11A
  • C = 12.6A
  • VA_total = 3036VA

Panel SB5

  • A = 10A
  • B = 42A
  • C = 37A
  • VA_total = 10680VA

VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.

Room 509 VA_total = 32916 VA

Assuming VA = W (PF should not affect heat dissipation)...

  • Room 509 BTU/h = 112309 BTU/h
  • Room 509 tons = 9.36 tons