BXadmin:Power
From CCGB
Panels
UPSes
PDUs
Measurements
OPP Panel measurements
Jun 02, 2010
Panel CRP
- A = 0
- B = 0
- C = 0
VA_total = 0
Panel CRP2
- A = 55A
- B = 45A
- C = 60A
VA_total = 19200VA
Panel P509
- A = 1.7A
- B = 11A
- C = 12.6A
VA_total = 3036VA
Panel SB5
- A = 10A
- B = 42A
- C = 37A
VA_total = 10680VA
VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.
Room 509 VA_total = 32916 VA
Assuming VA = W (PF should not affect heat dissipation)... Room 509 BTU/h = 112309 BTU/h Room 509 tons = 9.36 tons