BXadmin:Power
From CCGB
Contents
Panels
UPSes
PDUs
Measurements
Conversions used:
- 1 watt = 3.41214 BTU/h
- 1 ton = 12,000 BTU/h
Therefor, 1 ton = 3516.854 watts
OPP Panel measurements
Jun 02, 2010
Panel CRP
- A = 0
- B = 0
- C = 0
- VA_total = 0
Panel CRP2
- A = 55A
- B = 45A
- C = 60A
- VA_total = 19200VA
Panel P509
- A = 1.7A
- B = 11A
- C = 12.6A
- VA_total = 3036VA
Panel SB5
- A = 10A
- B = 42A
- C = 37A
- VA_total = 10680VA
VA was calculated assuming Line-Neutral voltage of 120V, and assuming no neutral current.
Room 509 VA_total = 32916 VA
Assuming VA = W (PF should not affect heat dissipation)...
- Room 509 BTU/h = 112309 BTU/h
- Room 509 tons = 9.36 tons
June 09, 2011
- RACK-1 =
- PDU-18[8+5 @208] -> UPS-13 -> SB5/14-16 = 2704W
- ((zeus[3.4 @120 + pc9[.5 @120]) -> PDU-14) + mulligan[3 @120] + jayne[1 @120]) -> UPS-12 = 940W
- RACK-2 =
- (ift-1 + comandra) -> PDU-19 -> UPS-15 -> P509/5-7 = 1000W
- xraid[ @120] -> UPS-9 =
- (herbie[3 @120] + pc4[.5 @120] + horvitz[3 @120] + tortuga[2 @120]) -> UPS-10 = 1020W
- RACK-3 =
- (galaxy nodes + pc8) -> PDU-20[11+6 @208] -> UPS-8 -> SB5/15-17 = 3536W
- RACK-4 =
- (PDU-21[8+11 @208] + thumper[5.8 @208])-> UPS-7 -> SB5/21-23 = 5158W
- RACK-5 =
- 12*dell_nodes[2 @120] -> PDU-17 = 2880W
- (1/2md1k-big[4 @120] + 1/2s1-array[2 @120] + 1/2md1k-1[2 @120] + 1/2md1k-4[2 @120] + 1/2md1k-5[2 @120] + 1/2c14) -> UPS-5
- (c8[2 @120] + foundry[.5 @120] + pc7[.5 @120] + 1/2s1-array[2 @120] + 1/2md1k-4[2 @120] + 1/2md1k-6[2 @120] + 1/2c14) -> UPS-6 -> CRP2-16
- RACK-6 =
- (node007..node012)[6*1.5 @120] -> PDU-6 -> CRP2-11 = 1080W
- (node001..node006)[6*1.5 @120] -> PDU-7 = 1080W
- (node013 + node014 + node015..node018)[6*1.5 @120] -> PDU-8 -> CRP2-1 = 1080W
- (node025..node032)[8*1.5 @120] -> PDU-9 -> CRP2-14 = 1440W
- (node019..node024)[6*1.5 @120] -> PDU-10 = 1080W
- (1/2lux[1] + 1/2s2[1] + 1/2s3[1] + 1/2md1k-3[1] + 1/2linne[.75] + 1/2xraid) -> UPS-2
- (1/2xraid + 1/2s2 + 1/2s3 + 1/2lux + 1/2md1k-3 + 1/2md1k-2) -> UPS-3
- (1/2md1k-2 + 1/2md1k-1 + 1/2md1k-5 + 1/2md1k-6 + 1/2md1k-big) -> UPS-4
- RACK-7 =
- (okinawa + switch) -> PDU-4 -> UPS-1
- (9 okinawa nodes) -> PDU-5 -> P509/6-8
- (7 okinawa nodes) -> PDU-22 -> CRP2/15-17
- (huck md1k and PE2850) -> CRP2/11
- RACK-8 =
- PDU-23[2+1 @208] -> UPS-14 -> P509/9-11 = 624W
machine current reference
- zeus = 1.7A x2 @120V
- carbonite promise sata RAID = 0.75A x2 @120V
- carbonite = 3.7A x2 @120V
- v880 2/3 power supplies, 3 CPU boards = ~5A x2 @120V
(10) PE 1950 - 2x Quad Core 2.83GHz, 16GB RAM, 146GB 15K 3.5" SAS, 1 PS powered off - 0.26A @120V pk, 0.16A @120V avg OS running, no load - 1.85A @120V pk, 1.73A @120V avg OS running, make -j32 - 2.73A @120V pk, 2.25A @120V avg (32) linne darwin compute node powered off - 0.20A @120V pk, 0.10A @120V avg OS running, no load - 1.40A @120V pk, 1.15A @120V avg OS running, forked du -hs /scratch - 1.83A @120V pk, 1.65A @120V avg (2) Xserve RAID 7.6A/3.6A (4) MD1K - 12x 3.5" SATA 2x C13 2.00A @208V Foundry EdgeIron 48W (.4A@120, .2A@208) (10) Okinawa and compute nodes, 8x Xeon 4.0A@120, 2.0A@208 SunFire 480R - 2x 1.2GHz US3+, 8GB (pilica) 3.2A@120 StorEdge 3300 1.5A@120 OptiPlex GX240 (minidb) 3/1.5 ? (10) PowerEdge 2650 (galaxy cnode) 2.5A@120, 1.25A@208 PE 2950 - 8x2.83GHz, 32gb, 6x 3.5" SATA (baker) 4A/2A PE 2950 - 8x2.83GHz, 32gb, 4x 2.5" SAS (badger) 3.74A/1.87A PE 2970 - 8xAMD 2356, 16gb, 6x 3.5" sata (apollo) 3.3A/1.65A IBM x3550 - 4x3.0GHz Xeon 5160, 32gb (atlas) ~3A/1.5A ? (2) IBM x3550 - 8x3.16GHz Xeon 5460, 32gb (c10, c11) ~4A/2A ? IBM x3550 - 4x2.66GHz Xeon 5150, 32gb (frisell) ~3A/1.5A ? Relion 230 - 4x2.8GHz Xeon, 2gb, 6x 3.5" PATA (horvitz) ~3/1.5A ? Relion 140 - 4x2.8GHz Xeon, 3gb, 1x 146GB U320 scsi (tortuga) ~2A/1A ? Altus 3150 - 2xAMD 250, 4gb, bunch o' sata (herbie) ~3A/1.5A ? Relion 2000 - 4x2.8GHz Xeon, 4gb, 3ware 9500s-8 (8 3.5" sata) (scofield) ~3/1.5 ? Altus 1300 - 2xAMD 256, 8gb, 2x 3.5" sata (mulligan) ~3/1.5 ? IBM x3455 - 4x AMD 2218, 4gb, ? (coltrane) ~3/1.5 ? IBM DS4200 - 8x 3.5" SATA, 2x 4Gb FC RAID ~4/2 ? Sun x4540 (thumper) 10/5.8